Transformer Scott Connection MCQ Quiz - Objective Question with Answer for Transformer Scott Connection - Download Free PDF

Last updated on Jun 13, 2025

Latest Transformer Scott Connection MCQ Objective Questions

Transformer Scott Connection Question 1:

Which of the following is a significant feature of Scott connection transformers?

  1. They provide high voltage output
  2. They convert 1-phase power into 3-phase
  3. They provide a 2-phase output from a 3-phase input. 
  4. They are used for stepping down voltage only.

Answer (Detailed Solution Below)

Option 3 : They provide a 2-phase output from a 3-phase input. 

Transformer Scott Connection Question 1 Detailed Solution

Explanation:

Scott Connection Transformers

Definition: A Scott connection transformer, also known as a Scott-T transformer, is a type of transformer connection used to convert a three-phase electrical power supply into a two-phase power supply and vice versa. This connection is primarily employed in industrial applications where two-phase power is required, such as in the operation of certain types of electrical motors or systems.

Working Principle:

The Scott connection transformer operates by using two transformers: the main transformer and the teaser transformer. The primary winding of the main transformer is connected across two lines of a three-phase supply, while the primary winding of the teaser transformer is connected between the third line and the center-tap of the main transformer’s primary winding. By carefully selecting the turns ratio of the windings, a balanced two-phase output can be obtained. The two-phase output has a 90° phase difference, which is the defining characteristic of two-phase systems.

Advantages of the Scott Connection:

  • Efficient conversion between three-phase and two-phase power, enabling the use of two-phase equipment in systems powered by three-phase supply.
  • Provides a balanced load on the three-phase supply, reducing the risk of unbalanced current and associated issues.
  • Simplifies the integration of legacy two-phase systems into modern three-phase infrastructure.

Applications: Scott connection transformers are widely used in applications such as:

  • Supplying power to two-phase motors and other two-phase equipment.
  • Traction systems in electric railways, where two-phase power is sometimes required.
  • Converting power in industrial facilities with a mix of three-phase and two-phase systems.

Correct Option Analysis:

The correct option is:

Option 3: They provide a 2-phase output from a 3-phase input.

This option accurately describes the primary feature of Scott connection transformers. These transformers are designed to convert three-phase electrical power into two-phase power, which is essential for operating two-phase equipment in systems powered by three-phase electricity. The Scott connection ensures a balanced two-phase output with a 90° phase difference, maintaining the integrity of the power supply and enabling efficient operation of two-phase loads.

Additional Information

To further understand the analysis, let’s evaluate the other options:

Option 1: They provide high voltage output.

This statement is incorrect in the context of Scott connection transformers. While transformers, in general, can step up or step down voltage, the Scott connection specifically refers to the method of converting three-phase power into two-phase power. The voltage level of the output depends on the turns ratio of the transformer windings, but this is not the primary feature of a Scott connection transformer.

Option 2: They convert 1-phase power into 3-phase.

This option is incorrect as it describes a different type of power conversion. Converting single-phase power into three-phase power typically requires a phase converter or a rotary transformer, not a Scott connection transformer. The Scott connection is specifically designed for converting three-phase power into two-phase power or vice versa.

Option 4: They are used for stepping down voltage only.

This option is misleading as it limits the functionality of Scott connection transformers. While these transformers can step down voltage if designed to do so, their primary purpose is to convert three-phase power into two-phase power. Voltage transformation is a secondary consideration and depends on the specific application and design of the transformer.

Conclusion:

The Scott connection transformer is a specialized device used for converting three-phase power into two-phase power, making it invaluable in applications where two-phase equipment needs to operate within a three-phase system. By understanding its working principle and advantages, it is clear that the correct option is Option 3, as it accurately describes the main feature of Scott connection transformers. Evaluating the other options highlights common misconceptions and underscores the importance of recognizing the specific function of Scott connection transformers in electrical systems.

Transformer Scott Connection Question 2:

Scott connection in transformers is primarily used for:

  1. Voltage regulation
  2. Power factor correction
  3. Harmonic reduction
  4. Three-phase to two-phase conversion

Answer (Detailed Solution Below)

Option 4 : Three-phase to two-phase conversion

Transformer Scott Connection Question 2 Detailed Solution

Scott (T-T) connection:

F2 J.P Madhu 21.05.20 D1

Explanation:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and two-phase to three-phase conversion.
  • Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to lines B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to line terminal A and the center tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.
  • So that in T-T connection, the percentage tapping of main transformer and teaser transformer respectively are 50% and 86.6%
     

Applications:

  • The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
  • It is used to supply the single-phase loads such as electric trains which are so scheduled as to keep the load on the three-phase system as nearly as possible.
  • The Scott-T connection is used to link a 3-phase system with a two-phase system with the flow of power in either direction.

Transformer Scott Connection Question 3:

How are two transformers connected in Scott-T connection?

  1. both electrically and magnetically
  2. Electrically
  3. Magnetic
  4. By using the Teaser Transformer

Answer (Detailed Solution Below)

Option 2 : Electrically

Transformer Scott Connection Question 3 Detailed Solution

Concept:

F2 J.P Madhu 21.05.20 D1

 

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is centre-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to the line terminal A and the centre tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.

 

Application:

  • The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
  • It is used to supply the single phase loads such as electric train which are so scheduled as to keep the load on the three phase system as nearly as possible.
  • The Scott-T connection is used to link a 3-phase system with a two–phase system with the flow of power in either direction.

 

Note:

  • The Scott-T connection permits conversions of a 3-phase system to a two-phase system and vice versa. But since 2-phase generators are not available, the converters from two phases to three phases are not used in practice.

Transformer Scott Connection Question 4:

Which of the following is correct regarding secondary distribution?

I. Secondary distribution distributes energy at customer utilization voltages from distribution transformers up to meters at customer's premises

II. In residential areas, 120/240 - V, single - phase, three - wire service is the most common, where lighting loads and outlets are supplied by 120 - V. single - phase connections, and large household appliances such as electric ranges, clothes dryers, water heaters, and electric space heating are supplied by 240 - V, single - phase connections

  1. Neither I nor II
  2. Only I
  3. Only II
  4. Both I and II

Answer (Detailed Solution Below)

Option 4 : Both I and II

Transformer Scott Connection Question 4 Detailed Solution

```html

The correct answer is Both I and II.

Key Points

  • Secondary distribution refers to the process of distributing electrical energy at customer utilization voltages from distribution transformers up to meters at customer's premises.
  • In residential areas, the 120/240-V, single-phase, three-wire service is the most common configuration.
  • Lighting loads and outlets are supplied by 120-V, single-phase connections.
  • Large household appliances such as electric ranges, clothes dryers, water heaters, and electric space heating are supplied by 240-V, single-phase connections.

 Additional Information

  • Distribution Transformers
    • Distribution transformers are used to step down the voltage to a level suitable for customer use.
    • They are typically located on utility poles or on the ground in residential areas.
    • These transformers play a crucial role in ensuring the safe and efficient delivery of electricity to homes and businesses.
  • Electrical Service Configurations
    • The 120/240-V, single-phase, three-wire service is common in North America for residential applications.
    • This configuration allows for both 120-V and 240-V electrical circuits, accommodating a variety of household appliances and lighting needs.
  • Usage of 240-V Connections
    • 240-V connections are used for high-power appliances that require more energy than typical 120-V outlets can provide.
    • Examples include electric ranges, clothes dryers, water heaters, and electric space heating systems.
```

Transformer Scott Connection Question 5:

Which of the following connections is used to supply power to a two-phase apparatus from a three - phase source and to supply power to a three - phase apparatus from a three - phase source?

  1. Delta - delta connection
  2. Open delta connection
  3. Scott - T connection
  4. Star-delta connection

Answer (Detailed Solution Below)

Option 3 : Scott - T connection

Transformer Scott Connection Question 5 Detailed Solution

Concept:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to lines B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to line terminal A and the center tapping D. It has primary AD and secondary b1b2.
  • The identical, interchangeable transformers are used for the Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has a primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.

Top Transformer Scott Connection MCQ Objective Questions

In T-T connection, the percentage tapping of main transformer and teaser transformer respectively are

  1. 50%, 86.6%
  2. 50%, 5%
  3. 86.6%, 86.6%
  4. 86.6%, 50%

Answer (Detailed Solution Below)

Option 1 : 50%, 86.6%

Transformer Scott Connection Question 6 Detailed Solution

Download Solution PDF

Scott (T-T) connection:F2 J.P Madhu 21.05.20 D1

Concept:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is centre-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to the line terminal A and the centre tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.
  • So that in T-T connection, the percentage tapping of main transformer and teaser transformer respectively are 50% and 86.6%

 

Application:

  • The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
  • It is used to supply the single phase loads such as electric train which are so scheduled as to keep the load on the three phase system as nearly as possible.
  • The Scott-T connection is used to link a 3-phase system with a two–phase system with the flow of power in either direction.

 

Note:

  • The Scott-T connection permits conversions of a 3-phase system to a two-phase system and vice versa. But since 2-phase generators are not available, the converters from two phases to three phases are not used in practice.

Scott connected transformers can convert
(a) three-phase to two-phase
(b) two-phase to three-phase
(c) two-phase to four-phase
(d) three-phase to four-phase.
From the above options correct answer is:

  1. a and c
  2. b and c
  3. b and d
  4. a and b

Answer (Detailed Solution Below)

Option 4 : a and b

Transformer Scott Connection Question 7 Detailed Solution

Download Solution PDF

Scott (T-T) connection:

F2 J.P Madhu 21.05.20 D1

Explanation:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and two-phase to three-phase conversion.
  • Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to lines B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to line terminal A and the center tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.
  • So that in T-T connection, the percentage tapping of main transformer and teaser transformer respectively are 50% and 86.6%

Applications:

  • The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
  • It is used to supply the single-phase loads such as electric trains which are so scheduled as to keep the load on the three-phase system as nearly as possible.
  • The Scott-T connection is used to link a 3-phase system with a two-phase system with the flow of power in either direction.

Which type of connection is used in transformers to link a 3-phase system with a 2-phase system with the flow of power in either direction? 

  1. Delta star
  2. Star delta 
  3. V–V connection
  4. T–T connection

Answer (Detailed Solution Below)

Option 4 : T–T connection

Transformer Scott Connection Question 8 Detailed Solution

Download Solution PDF

The correct answer is option 4):

Concept:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and two-phase to three-phase conversion. Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically. One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer. The main transformer is centre-tapped at D and is connected to lines B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to line terminal A and the centre tapping D.
  • It has primary AD and secondary b1b2. The identical, interchangeable transformers are used for the Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has a primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer. So that in the T-T connection, the percentage tapping of the main transformer and teaser transformer respectively are 50% and 86.6%

F2 J.P Madhu 21.05.20 D1

Which of the following connections is used to supply power to a two-phase apparatus from a three - phase source and to supply power to a three - phase apparatus from a three - phase source?

  1. Delta - delta connection
  2. Open delta connection
  3. Scott - T connection
  4. Star-delta connection

Answer (Detailed Solution Below)

Option 3 : Scott - T connection

Transformer Scott Connection Question 9 Detailed Solution

Download Solution PDF

Concept:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to lines B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to line terminal A and the center tapping D. It has primary AD and secondary b1b2.
  • The identical, interchangeable transformers are used for the Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has a primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.

Scott-T transformer connection is used for the conversion of

  1. Three phase to single phase
  2. Single phase to two phase
  3. Single phase to three phase
  4. Three phase to two phase

Answer (Detailed Solution Below)

Option 4 : Three phase to two phase

Transformer Scott Connection Question 10 Detailed Solution

Download Solution PDF

Concept:

F2 J.P Madhu 21.05.20 D1

 

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is centre-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to the line terminal A and the centre tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.

 

Application:

  • The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
  • It is used to supply the single phase loads such as electric train which are so scheduled as to keep the load on the three phase system as nearly as possible.
  • The Scott-T connection is used to link a 3-phase system with a two–phase system with the flow of power in either direction.

 

Note:

  • The Scott-T connection permits conversions of a 3-phase system to a two-phase system and vice versa. But since 2-phase generators are not available, the converters from two phases to three phases are not used in practice.

In scott connections, the teaser transformer operates on 0.866 of its rated ________.

  1. Inductance
  2. Capacitance
  3. Reactance
  4. Voltage

Answer (Detailed Solution Below)

Option 4 : Voltage

Transformer Scott Connection Question 11 Detailed Solution

Download Solution PDF

Scott connection:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to the line terminal A and the center tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.

Scott connection is used for the conversion of

  1. single-phase to three-phase
  2. single-phase to two-phase
  3. three-phase to two-phase
  4. All of the above

Answer (Detailed Solution Below)

Option 3 : three-phase to two-phase

Transformer Scott Connection Question 12 Detailed Solution

Download Solution PDF
  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to the line terminal A and the center tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.

__________ connection is the most common method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.

  1. Star-delta
  2. Delta-delta
  3. Star-star
  4. Scott

Answer (Detailed Solution Below)

Option 4 : Scott

Transformer Scott Connection Question 13 Detailed Solution

Download Solution PDF

Scott (T-T) connection:

F2 J.P Madhu 21.05.20 D1

Concept:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is centre-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to the line terminal A and the centre tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.
  • So that in T-T connection, the percentage tapping of main transformer and teaser transformer respectively are 50% and 86.6%

 

Application:

  • The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
  • It is used to supply the single phase loads such as electric train which are so scheduled as to keep the load on the three phase system as nearly as possible.
  • The Scott-T connection is used to link a 3-phase system with a two–phase system with the flow of power in either direction.

 

Note:

  • The Scott-T connection permits conversions of a 3-phase system to a two-phase system and vice versa. But since 2-phase generators are not available, the converters from two phases to three phases are not used in practice.

In Scott connection, the voltage across the teaser leads the mains by

  1. 120°
  2. 90°
  3. 60°
  4. 30°

Answer (Detailed Solution Below)

Option 2 : 90°

Transformer Scott Connection Question 14 Detailed Solution

Download Solution PDF

Scott Connection:

622587c0a55ebdcc8a99c737 16493486586061

  • The Scott Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • Scott connection of transformer is also known as T-T connection.
  • One of the transformers is called the main transformer and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2
  • The teaser transformer is connected to line terminal A and the centre tapping D.  It has primary AD and secondary b1b2
  • The voltage across the teaser leads the mains supply by \(90^{\circ}\)
  •  The three phases of primary side of the main transformer have a tapping of 0.289Tp, 0.5Tp, and 0.5Tp where Tis the no. of turns on the primary side.
  • The teaser transformer has a primary voltage rating equal to 0.866 times the voltage rating of the main transformer.

Which of the following three-phase transformer connections is called a T-T connection?

  1. Star-delta connection
  2. Star-star connection
  3. Scott connection
  4. Open delta connection

Answer (Detailed Solution Below)

Option 3 : Scott connection

Transformer Scott Connection Question 15 Detailed Solution

Download Solution PDF

The correct answer is (option 3) i.e. Scott connection.

Explanation:

Scott (T-T) connection:

F2 J.P Madhu 21.05.20 D1

Concept:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • Scott connection of transformer is also known as T – T connection.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is centre-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to line terminal A and the centre tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for the Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.
  • So that in T-T connection, the percentage tapping of main transformer and teaser transformer respectively are 50% and 86.6%

 

Application:

  • The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
  • It is used to supply the single phase loads such as electric trains which are so scheduled as to keep the load on the three-phase system as nearly as possible.
  • The Scott-T connection is used to link a 3-phase system with a two-phase system with the flow of power in either direction.

 

Note:

  • The Scott-T connection permits conversions of a 3-phase system to a two-phase system and vice versa. But since 2-phase generators are not available, the converters from two phases to three phases are not used in practice.
Get Free Access Now